RS-485 Termination: Where to Place the End Resistors

RS-485 termination limits reflections at the ends of a cable. On a typical two-wire multipoint trunk using 120 Ω cable, termination is commonly installed at the two physical ends. Draw the cable route and check integrated termination switches before adding a resistor to any device.
Find the physical ends of the trunk
The controller can sit in the middle of the bus. Trace where the main cable actually starts and ends, and mark any long branches or star wiring. Adding a resistor to a middle device can load the driver without addressing reflections at an unterminated end. The RS-485 cable guide explains how cable impedance and routing relate to the bus layout.
Match the resistor to the cable and devices
Texas Instruments' RS-485 design guide describes 120 Ω termination at each end of a typical 120 Ω trunk. Check the actual cable specification and the equipment manual. Identify external resistors and built-in switchable resistors before changing either. Keep any stub short enough for the actual signal edge rate and cable propagation delay.

Interpret a resistance check with the bus isolated
On a de-energized, isolated bus, two ideal 120 Ω resistors in parallel read about 60 Ω across the pair. A reading near 120 Ω can indicate one visible termination. Biasing networks, other circuitry, and cable resistance can alter the reading. Compare it with the wiring diagram and avoid using resistance alone to infer where the resistors are installed.
Keep termination and idle bias separate
Termination addresses reflections, while biasing establishes an idle differential voltage when no driver is active. Review both functions if readings are intermittent. The RS-485 biasing guide covers the idle state. If the link is stable but values are wrong, the Modbus register troubleshooting guide covers the distinction between communication and value interpretation.
Frequently asked questions
Does every short bus need external resistors?
Follow the transceiver and network design guidance. The need depends on electrical length, signal edge rate, and device loading. Verify communications with the installed arrangement before treating any bench result as representative.