YF500-R32/R454 Refrigerant Gas Leak Sensor
ODSENSE

YF500-R32/R454 Refrigerant Gas Leak Sensor

The YF500-R32/R454 is a refrigerant gas monitoring sensor for suitable HVAC and refrigeration installations.

Refrigerant gas monitoring

Technical specifications

Technical Specification
ParameterSpecification
Detection GasR32 / R454A / R454B / R454C
Detection PrincipleNDIR (Non-Dispersive Infrared)
Measurement Range0~50 LFL
Accuracy±2.5% LFL
Response Time≤12s
Warm-up Time0s
Service Life>15 Years
Technical Specification
ParameterSpecification
Power SupplyDC10~30V (24V Standard)
Power Consumption0.18W
Digital OutputRS485 Modbus RTU
Analog Output4-20mA / 0-5V
Wireless CommunicationLoRaWAN / WiFi / Bluetooth / 4G
Protection RatingIP65
Housing MaterialFlame-retardant ABS
InstallationWall Mount / Pipe Mount
Model Selection / Ordering Information
ModelCommunicationApplication
YF500-R32(R)RS485HVAC Monitoring System
YF500-R32(L)LoRaWANWireless Remote Monitoring
YF500-R32(W)WiFiIoT Cloud Platform
YF500-R32(20)4-20mAIndustrial Controller Integration
YF500-R32(V5)0-5VAnalog Data Acquisition

YF500-R32/R454 refrigerant gas leak sensor

The YF500-R32/R454 is intended for refrigerant gas monitoring in HVAC and refrigeration installations. The product specifications identify R32 and R454A, R454B and R454C detection options and an NDIR sensing principle. Specify the refrigerant and the required communication configuration when selecting a version.

Plan the monitoring application

Refrigeration equipment can be installed in machinery rooms, cold stores, commercial buildings and other spaces with different ventilation and maintenance arrangements. Identify the refrigerant, potential release locations and the areas that require monitoring as part of the system design.

Sensor position and the response to a possible leak should be determined using the equipment documentation, applicable requirements and the site’s safety plan. Provide access for maintenance and avoid placing the sensing area where airflow or a physical obstruction prevents it from sampling the intended environment.

Measurement and output selection

The specifications list ±2.5% LFL accuracy and a response time of ≤12 seconds.

RS485 Modbus RTU, analog and wireless communication options are listed for different versions. Select the ordering code that matches the receiving controller or gateway, and confirm the power supply, signal and network arrangement. Interface options should not be assumed to be fitted together in every unit.

Installation and commissioning

Follow the installation instructions for the selected refrigerant and enclosure. Consider equipment layout, ventilation, accessibility and the possibility of physical damage or contamination. Record the installed model, detected gas and communication settings so that the monitoring system and maintenance records refer to the correct device.

Commission the installation using the approved procedure and check that readings reach the receiving system. Alarm logic, notification and response procedures are part of the complete site design and should be verified for the intended application.

Integrating monitoring into an HVAC project

Start with an equipment schedule identifying the refrigerant used in each system and the locations where monitoring is required. Agree how measurements will be transmitted, displayed and reviewed, and how any alarm or device fault will be communicated to the responsible personnel. Check compatibility with the selected controller and the project’s network before fixing the cable route or gateway position.

During handover, document each sensor location, the configured gas and interface, commissioning results and the maintenance contact. If equipment or refrigerant changes later, review the monitoring arrangement and verify that the installed sensor configuration remains appropriate for the revised system.

Inspection and product selection

Inspect the sensing area, enclosure and connections periodically. Follow the supplied instructions for testing, cleaning and calibration, and review the maintenance schedule against the actual operating environment. For an enquiry, provide the refrigerant, expected monitoring conditions, number of points and required interface.