Ventilation airflow monitoring
Technical specifications
| Parameter | Specification |
|---|---|
| Operating Voltage | DC 10V~30V (Standard 24V) |
| Operating Current | ≤200mA (@5V Power Supply) |
| Warm-up Time | 2 Minutes |
| Sampling Rate | Once per second (Default) |
| Standard Output | RS485 Modbus RTU |
| Optional Communication | LoRaWAN / WiFi / 4G |
| Housing Material | Flame-Retardant ABS Enclosure |
| Mounting | Pipe Mount / Wall Mount |
| Main Unit Dimensions | 124 × 94 × 45 mm |
| Parameter | Specification |
|---|---|
| Operating Temperature | -30°C ~ 80°C |
| Operating Humidity | 0 ~ 99%RH (Non-condensing) |
| Protection Rating | IP67 |
| Detection Type | Range | Resolution | Accuracy | Starting Wind Speed |
|---|---|---|---|---|
| Air / Nitrogen / Exhaust Fumes | 0 ~ 30 m/s | 0.1 m/s | ±3% | 0.1 m/s |
| Model | Communication | Application |
|---|---|---|
| YF500-AIR(R) | RS485 Modbus RTU | HVAC, PLC and wired ventilation monitoring systems |
| YF500-AIR(L) | LoRaWAN | Large-area wireless industrial and agricultural monitoring |
| YF500-AIR(W) | WiFi | Smart buildings, laboratories and local network applications |
| YF500-AIR(G) | 4G | Remote air velocity monitoring without local network access |
YF500-AIR air velocity transmitter
The YF500-AIR monitors air velocity for ventilation and environmental monitoring installations. Its listed measurement range is 0–30 m/s, with 0.1 m/s resolution and ±3% accuracy. The listed standard output is RS485 Modbus RTU, and other communication versions can be selected for compatible systems.
Measure airflow where it matters
Air velocity can vary across a duct or room and can change with fan speed, dampers and operating conditions. A sensor measures at its sensing location; one point should not automatically be treated as the average for an entire duct or space. Choose measurement locations around the operating question and the installation’s airflow pattern.
In ventilation systems, consider bends, transitions, fans and other features that can disturb flow. Select a position with suitable access and follow the supplied installation instructions. Record the location and operating conditions so that later readings can be compared meaningfully.
Review the measurement range
The listed detection table identifies air, nitrogen and exhaust fumes with a 0–30 m/s range and 0.1 m/s starting wind speed. Review the medium, temperature and exposure with the project requirements before selecting the device. Confirm the applicable accuracy conditions and whether the sensor materials are suitable for the actual air stream.
The product table separately lists an operating temperature of −30 to 80 °C and non-condensing humidity of 0–99% RH. Check the limits for the complete installation, including the probe, enclosure and cabling.
Connect to a monitoring system
The R configuration is listed with RS485 Modbus RTU. L, W and G versions are listed for LoRaWAN, WiFi and 4G. Select the output that matches the controller or gateway and confirm power, protocol settings and any network equipment for the ordered version. Wireless options are not implied to be included together.
Installation and maintenance
Provide a secure mounting location and protect the cable from physical damage. Keep the sensing region clear of obstructions and follow the approved instructions for orientation, cleaning and maintenance. Where dust, grease or other deposits are present, plan inspection for the actual conditions rather than relying on a generic cleaning interval.
During commissioning, check the signal and compare readings using the site’s reference procedure. Note the installed position, range, interface and any later changes to the ventilation system. Explore the industrial sensor range and industrial monitoring solution for related measurements.
Selection and integration
Industry applications
- HVAC engineering
- Commercial buildings
- Manufacturing