NDIR CO2 Sensors: How They Work and Where to Install Them

NDIR CO2 Sensors: How They Work and Where to Install Them

An NDIR CO2 sensor estimates carbon dioxide concentration by measuring how gas in a chamber absorbs infrared light. It can support indoor environmental monitoring, ventilation investigation and other applications when the instrument is correctly selected and placed. A CO2 reading is useful context, but it does not measure every indoor contaminant or independently establish that a space is safe.

This guide explains the measurement principle, practical installation considerations and the information needed to compare instruments. It describes NDIR technology generally; the sensing principle and available features of a particular ODSENSE product must be checked against that model's documentation.

How does NDIR measurement work?

NDIR means non-dispersive infrared. A typical sensor includes an infrared source, a chamber through which the sampled gas passes, an optical filter and a detector. Carbon dioxide absorbs light at characteristic wavelengths. The instrument compares the detected signal with its reference or calibration model and reports an estimated CO2 concentration, commonly in parts per million (ppm).

The sensor measures the gas reaching its chamber, not the entire room at once. Sampling design, airflow, contamination and sensor condition can influence the reading. Pressure and temperature may also affect the measurement or its compensation, depending on the instrument. Review the specifications and operating instructions for the model in use.

What can CO2 tell you about ventilation?

In occupied spaces, people exhale CO2. Its concentration can therefore provide useful information about how occupied air and outdoor air are mixing over time. Compare the trend with occupancy, room use and ventilation operation rather than treating one instantaneous value as a complete assessment.

CO2 does not directly measure particles, carbon monoxide, volatile organic compounds or every airborne hazard. Air-cleaning devices may remove some pollutants without removing CO2. The UK Health and Safety Executive guidance discusses limitations when CO2 monitors are used to evaluate ventilation. Select additional measurements according to the actual sources and decision.

NDIR CO2 Sensors: How They Work and Where to Install Them

Place the monitor where the reading is useful

Choose a location representative of the occupied zone or process being monitored. Avoid direct exhaled breath, a supply-air jet, open windows, doors and other strongly local influences unless the goal is specifically to investigate them. Do not hide the sensor behind furniture or in stagnant pockets. Consider security, power, access and the manufacturer's mounting instructions.

Large or irregular spaces may need several points, because CO2 can vary within a room. Observe normal occupancy cycles and compare positions during commissioning. EPA sensor siting guidance provides broader considerations for selecting an indoor measurement location.

Compare specifications at the expected operating point

Select a measuring range that covers the intended application and likely excursions. Compare accuracy over that range, warm-up requirements, response time, environmental limits and long-term maintenance. Resolution is not the same as accuracy. Check whether pressure compensation, temperature compensation, a display or a particular communication protocol is included in the actual version being purchased.

Automatic baseline correction is available on some instruments, but its assumptions matter. A location that rarely returns to an appropriate fresh-air baseline may not suit a particular automatic calibration strategy. Confirm the manufacturer's guidance before enabling it, and document any adjustment. Do not apply a calibration method intended for one design to a different sensor without checking.

Connect measurements to action

Define what the operator should do when the trend changes: review occupancy, check the ventilation schedule, inspect a damper or investigate a sensor fault. Use the building's operating context and applicable guidance when choosing alert settings. A single universal threshold cannot describe every room and use case.

For integration, agree on power, output signal, register mapping, data frequency and network addressing. RS485 Modbus may be an option on some devices; availability depends on the model and configuration. Explore indoor air quality sensors and industrial environment monitoring for related measurement and system-planning considerations.

Maintain confidence in the data

Keep a record of the model, serial number, placement, firmware or configuration, calibration method and maintenance history. Periodically check the air inlet for blockage and compare readings with a suitable reference using the manufacturer's procedure. Allow instruments to stabilise together in the same location before interpreting differences. A persistent mismatch needs investigation; it is not proof that either device is correct without a traceable reference and appropriate method.

When a sensor is moved, record the change. Apparent improvements or deterioration may reflect a new location rather than a change in ventilation. Review suspicious flat lines, abrupt steps and readings outside the configured range alongside equipment and occupancy logs.

Frequently asked questions

Does an NDIR CO2 monitor detect carbon monoxide?

An instrument described as a CO2 sensor measures CO2; carbon monoxide requires a suitable separate sensing channel. Confirm the channels on the selected model.

Can CO2 alone prove that indoor air is safe?

No. CO2 can help interpret ventilation in an occupied space, but it does not measure every pollutant or replace an assessment of relevant hazards.

Should every monitor use automatic baseline correction?

No. The operating environment must satisfy the specific algorithm's assumptions. Follow the manufacturer's instructions and consider the consequences of an incorrect baseline.

Sources: HSE guidance on using CO2 monitors; EPA guidance on sensor placement; research on NDIR CO2 sensors.