EnglishEspañol — Borrador para revisión · Sin publicarPortuguês do Brasil — Rascunho para revisão · Não publicadoالعربية — مسودة للمراجعة · غير منشورةBahasa Indonesia — Draf untuk ditinjau · Belum diterbitkanFrançais — Brouillon à relire · Non publiéDeutsch — Entwurf zur Prüfung · Nicht veröffentlichtРусский — Черновик для проверки · Не опубликованTiếng Việt — Bản thảo để duyệt · Chưa xuất bảnไทย — ฉบับร่างสำหรับตรวจสอบ · ยังไม่เผยแพร่
ODSENSE · Technical insights

4–20 mA Scaling: Convert Current to Engineering Units

4–20 mA Scaling: Convert Current to Engineering Units

For linear 4–20 mA scaling, subtract 4 mA from the measured current and divide by 16 mA. Multiply that fraction by the configured engineering span and add the lower range value. Check the transmitter configuration before using the formula, especially for differential-pressure flow loops.

Use the configured endpoints

The lower and upper range values come from the configured transmitter output. They can differ from the sensor's full measurement capability. NI's scaling guide derives the scale from two known endpoints. In a worked example, a transmitter configured for −50 to 150 kPa reports 50 kPa at 12 mA because 12 mA is halfway through the current span.

Test at the range ends and midpoint

Under the site's authorized loop-test procedure, compare the device and receiver at 4, 12, and 20 mA or equivalent reference inputs. Note which unit the receiver expects, especially whether a software channel reports amperes, milliamperes, or raw counts. The 4–20 mA loop troubleshooting guide covers the electrical checks to run when the received current differs.

For a linear output, 4 mA maps to the lower range, 12 mA to the midpoint, and 20 mA to the upper range.
For a linear output, 4 mA maps to the lower range, 12 mA to the midpoint, and 20 mA to the upper range.

Find where square-root extraction happens

Flow inferred from differential pressure can use square-root extraction. If the transmitter already outputs a signal linear in flow, the receiver should scale that output as flow. If current is linear in pressure and the receiver calculates flow, apply its documented flow conversion there. A second extraction distorts the midrange. The Rosemount measurement manual gives an example of selectable transfer functions.

Preserve status as well as the calculated value

Determine how the transmitter and receiver represent underrange, overrange, and faults. Keep the raw current and quality flag where available. If the input is clipped to the displayed engineering range, an equipment fault may look like a valid endpoint. See the pressure signal selection guide and differential pressure guide for signal and measurement context.

Frequently asked questions

Does 4 mA always mean zero?

It represents the configured lower range value for a normal linear output. That engineering value can be positive, zero, or negative.