4–20 mA Scaling: Convert Current to Engineering Units

For linear 4–20 mA scaling, subtract 4 mA from the measured current and divide by 16 mA. Multiply that fraction by the configured engineering span and add the lower range value. Check the transmitter configuration before using the formula, especially for differential-pressure flow loops.
Use the configured endpoints
The lower and upper range values come from the configured transmitter output. They can differ from the sensor's full measurement capability. NI's scaling guide derives the scale from two known endpoints. In a worked example, a transmitter configured for −50 to 150 kPa reports 50 kPa at 12 mA because 12 mA is halfway through the current span.
Test at the range ends and midpoint
Under the site's authorized loop-test procedure, compare the device and receiver at 4, 12, and 20 mA or equivalent reference inputs. Note which unit the receiver expects, especially whether a software channel reports amperes, milliamperes, or raw counts. The 4–20 mA loop troubleshooting guide covers the electrical checks to run when the received current differs.

Find where square-root extraction happens
Flow inferred from differential pressure can use square-root extraction. If the transmitter already outputs a signal linear in flow, the receiver should scale that output as flow. If current is linear in pressure and the receiver calculates flow, apply its documented flow conversion there. A second extraction distorts the midrange. The Rosemount measurement manual gives an example of selectable transfer functions.
Preserve status as well as the calculated value
Determine how the transmitter and receiver represent underrange, overrange, and faults. Keep the raw current and quality flag where available. If the input is clipped to the displayed engineering range, an equipment fault may look like a valid endpoint. See the pressure signal selection guide and differential pressure guide for signal and measurement context.
Frequently asked questions
Does 4 mA always mean zero?
It represents the configured lower range value for a normal linear output. That engineering value can be positive, zero, or negative.